Intelligent Operator

5智能手操器DFD-4000.png
  • 5智能手操器DFD-4000.png
Intelligent hand manipulator is an intelligent instrument which can replace two instruments of servo…

Description:

Productoverview:

ZW-DFD/Q series Intelligent operator Is a smart meter servo amplifier operator to replace the traditional DDZ type automatic control system in the two meters. Using system on chip technology, single structure, superior performance, reliable quality, double beam three digital display, eye-catching appearance, with a variety of domestic and foreign intelligent regulator or DCS supporting the use of computer control system, fault and maintenance as the host backup manual output unit.

This series is divided into: D type Q type exercises, exercises, and manual control.

1, D type manipulator

D type manipulator is a control signal and the actuator by the controller or DCS send feedback to the valve position signal for operation, motor output directly reversing electrical signal drive electric actuator, control the motor positive inversion, while the output signal to the regulator valve. Automatic / manual operation device, switch state signal output to the regulator, as the regulator valve position signal tracking, i.e. when the regulator receives the manual state signal operator, the regulator valve position tracking.

2, Q type manipulator

Q type operator is a control signal transmitted from the controller and actuator or DCS feedback to the valve position signal after the operation, the linear output current or voltage signal of direct drive pneumatic valve, control valve switch, and the output signal to the regulator valve. Automatic / manual operation device, switch state signal output to the regulator, as a regulator valve position tracking signal, i.e. when the manual operator received signal regulator, regulator of valve position tracking.

3, manual control

Manual control device is a non operating device of automatic control, only receiving valve position signal, the control output through the man-machine dialogue, the output signal can be a positive signal (D manual control) or linear current voltage signal (Q manual control). And through the reception of the valve position signal, valve position display, to determine the valve opening.

Two, application:

ZW-DFD/Q series <strong style="white-space: normal;"> intelligent operation device</strong> for small and medium process device of temperature and pressure and other parameters of single loop control. Can be used in metallurgy, petroleum, chemical industry, building materials, paper, food, pharmaceutical, heat treatment and water treatment and other industrial field.

Three, the main function:

1, the input signal can be arbitrarily selected.

2, automatically boot or boot manual (manual output values can be preset).

3, automatic output.

4, process instructions, control instructions, valve position feedback indicating triple display.

5, can set the upper limit and lower limit output range respectively.

6, valve position feedback value of the analog output.

7, analog output control.

8, EM1 a remote manual function, the initial output value remains unchanged, remote manual function after the cancellation, can keep the manual or automatic state return.

9, EM2 a remote manual function, the initial output values can be preset.

10, valve position feedback error indication, valve position feedback line can automatically enter the manual mode.

11, tracking error error indication.

12, the main input line breakdown control signal output to the motor protection automatic (manual operation control), and outputs the fault alarm signal.

13, the instrument built-in two 40A triac, direct control of actuator motor reversing.

14, the instrument can also be an additional bit type control instrument (universal input). Manipulator with signal input calibration, a calibration instrument uses the E menu.

Four, technical parameters:

1, measurement accuracy: + 0.5%FS+1d + 0.2%FS+1d

2, analog output accuracy: the valve position feedback output and control output + 0.5%FS + 0.5%FS

3, analog output drive the load current signal: 0~10mA = 1.5K; 4~20mA = 750. Signal voltage: 0~5V, 1~5V output impedance is less than or equal to 1.

4, the analog input impedance signal: current: less than 50 ohm; the voltage signal is not less than 500K.

5, manual / automatic: automatic output state is broken through manual;

6, remote manual input EM1: low level switch, EM1 kinetic energy effectively, disconnect the invalid. Remote manual input EM2: low level switch, EM2 kinetic energy effectively, disconnect the invalid.

7, relay contact capacity: AC220V, 3A (resistive load)

8, parameter setting instrument after power-off hold time: more than 20 years

9, insulation strength: AC voltage 1500V, 1 minutes

10, insulation resistance: 50M ohm above

11, power supply: 220V, 50HZ, 6W or 24V

12, the requirements of working environment: temperature 0-50, relative humidity: less than 85%, no corrosive gas, no vibration.

Five, instrument installation:

1, dual display

A, on the digital display adjustment of PC display, set the parameters of the prompt to enter the parameter setting mode.

Under B, digital display control volume percentage or valve position feedback quantity percentage (please specify when ordering). The manual status as a percentage display output control. Enter the parameter setting mode display parameter setting.

2, double + single analog

A, on the digital display adjustment of PC display, set the parameters of the prompt to enter the parameter setting mode.

Under B, digital display control volume percentage or valve position feedback quantity percentage (please specify when ordering). The manual status as a percentage display output control. Enter the parameter setting mode display parameter setting.

C, analog display valve position feedback volume percentage.

3, single screen + double dummy bar

A digital tube display, adjust the amount of PC or valve position feedback signal or as a percentage amount as a percentage display display control, display and key switch. The manual status as a percentage display output control.Enter the parameter setting mode display parameter settings and prompt setting parameters.

B, the left analog control bar as a percentage of PC display or regulator output signal.

C, the right analog as a percentage display valve position feedback.

4, double screen + double dummy bar

A, on the digital display adjustment of PC display, set the parameters of the prompt to enter the parameter setting mode.

Under B, digital display control volume percentage or valve position feedback quantity percentage (please specify when ordering). The manual status as a percentage display output control. Enter the parameter setting mode display parameter setting.

C, the left analog control bar as a percentage of PC display or regulator output signal.

D, the right analog as a percentage display valve position feedback.

5, three screen display

A, on the digital display adjustment of PC display, set the parameters of the prompt to enter the parameter setting mode.

B, head of digital tube display valve position feedback percentage. The manual status as a percentage display output control. Enter the parameter setting mode display parameter setting.

C and a lower percentage of weight control digital tube display.

6 indicator light

A, the lamp is a positive turn indicator (DFD) or the control volume and valve position feedback positive deviation alarm indicator (DFQ).

E, light reversal indicator (DFD) or the control volume and valve position feedback negative deviation alarm indicator (DFQ)

C, lamp automatic indication lamp or SP4 alarm lamp.

G, light manual indicator lamp.

B, SP3 lamp alarm lamp.

D, lights for EM1 status indicator.

F, lights for EM2 status indicator.

Six, selection table:

ZW-DFExplain
Instrument typesDElectric
QPneumatic
Design sequenceFourIntelligent manipulator (Zhongwei control)
Display modeOneSingle screen + double beam
TwoDouble screen + Dan Guangzhu
ThreeDouble screen + double beam
FourThree screen display
Input modeOneWith direct current (0~10mA, 4~20mA)
TwoWith DC voltage (0~5V, 1~5V)
ThreeSpecial note in order of input signal

Control and output

Adjust the way

Electric manipulatorOneForward and reverse + upper and lower limit alarm
TwoForward and reverse + manual output
ThreeForward and reverse +EM1 function
FourForward and reverse +EM2 function
FiveForward and reverse + boot manual function
SixForward and reverse +, breadth limit function
Hand operated deviceOneDC output (0~10mA, 4~20mA) and the upper and lower limit alarm
TwoDC output (0~10mA, 4~20mA) + manual output
ThreeDC output (0~10mA, 4~20mA) +EM1
FourDC output (0~10mA, 4~20mA) +EM2
FiveDC output (0~10mA, 4~20mA) + boot manual function
SixDC output (0~10mA, 4~20mA) + upper and lower limiting function
The valve position feedback input modeZeroNo valve position feedback
OneFeedback 0~10mA
TwoFeedback 4~20mA
ThreeFeedback 0~5V
FourFeedback 1~5V
FiveFeedback 0~10V
SixFeedback potentiometer (order stated resistance)

DFExplain
SizeHThe 160 x 80The opening 152 x 76
VThe 80 x 160The opening 76 x 152
F96 * 96The opening 92 x 92
Q72 * 72The opening 68 x 68
The valve position feedback value transmission outputANo transmission output
BTransmission output 0~10mA
CTransmission output 4~20mA
DTransmission output 0~5V
ETransmission output 1~5V
FSpecial signal transmission output (the order stated)
Send control quantity outputANo transmission output
BTransmission output 0~10mA
CTransmission output 4~20mA
DTransmission output 0~5V
ETransmission output 1~5V
FSpecial signal transmission output (the order stated)
For 24V DC currentPThe default is no 24V output DC power supply
With 24V DC power supply output (as a two-wire transmitter power supply)
communication interfaceTThe default is not with communication interface
With RS485 or RS232 communication interface
Power supply

K

W

The default is 220V.AC
Switching power supply 85~260VAC
Switching power supply 18~36VDC or 18~36VAC

Customer service service commitment:

1, my company sold Zhongwei control product quality problems within twelve months, responsible for free maintenance.

2, the warranty period if the products of our company have any quality problems, our company is responsible for free repair or replacement.

3, the warranty period if the user use undeserved, cause damage to the product, our company is responsible for the maintenance, collect the damaged parts cost.

4, after the warranty period of product quality problems, our company is responsible for the maintenance, collect the damaged parts cost.

5, if the user needs to our service, our company in the province of the user service personnel arrived at the scene within 12 hours, arrived at the scene 48 hours outside users.